Synopsys
All newly installed air handlers with a mechanical cooling capacity over 33,000 Btu/hr and an installed air economizer shall include a stand-alone or integrated Fault Detection and Diagnostics (FDD) system. This article will discuss the requirements for that FDD system.
Requirements
- The following temperature sensors shall be permanently installed to monitor system operation: outside air, supply air, and when required for differential economizer operation, a return air sensor, and
- Temperature sensors shall have an accuracy of ±2°F over the range of 40°F to 80°F; and
- The controller shall have the capability of displaying the value of each sensor; and
- The controller shall provide system status by indicating the following conditions:
- Free cooling available;
- Economizer enabled;
- Compressor enabled;
- Heating enabled if the system is capable of heating; and
- Mixed-air low-limit cycle active.
- The unit controller shall allow manual initiation of each operating mode so that the operation of cooling systems, economizers, fans, and heating systems can be independently tested and verified; and
- Faults shall be reported in one of the following ways:
- Reported to an Energy Management Control System regularly monitored by facility personnel.
- Annunciated locally on one or more zone thermostats or a device within five (5) feet of the zone
thermostat(s), clearly visible, at eye level, and meeting the following requirements:
- On the thermostat, device, or an adjacent written sign, display instructions to contact appropriate building personnel or an HVAC technician; and
- In buildings with multiple tenants, the annunciation shall either be within the property
management offices or in a common space accessible by the property or building manager. - Reported to a fault management application which automatically provides notification of the
fault to a remote HVAC service provider.
- The FDD system shall detect the following faults:
- Air temperature sensor failure/fault;
- Not economizing when it should;
- Economizing when it should not;
- Damper not modulating; and
- Excess outdoor air.
- The FDD System shall be certified by the Energy Commission as meeting requirements of Subsections 120.2(i)1 through 120.2(i)7 in accordance with Section 110.0 and JA6.3.
Exception to Section 120.2(i)8: FDD algorithms based in direct digital control systems are not required to be certified by the Energy Commission
Comments
0 comments
Please sign in to leave a comment.